Section 14.5: Performance of a Round-Rotor Synchronous Generator cont.
Which yields E » 5495/19.2° V. so that
VR% = [(|VNL| - |VFL|)/|VFL|]´100% = [(|E| - |Vt|)/|Vt|]´100%
= [(5495 - 3811)V./3811V.]´100% » 44.2%
Calculate the % voltage regulation three-phase wye-connected 2.5 MVA, 6.6 KV synchronous generator operating at rated KVA load, 0.8 lagging power factor. The synchronous impedance is: Zs = Ra +jXs = (0.071 + j10.4)W